Comprehensive evaluation system and scoring standard of electrical fire risk assessment.
Comprehensive evaluation system of electrical fire risk weight A | Criterion layer | Index layer | 0points | 1-9points | 10points | |
Fire combustion risk B1 |
Peak heat release rate C1 (KW) |
C1<1500 | 1500≤C1≤3500 | 3500<C1 | ||
Time for the temperature of the hazard room to reach 200℃ C2(s) |
50<C2 | 20≤C2≤50 | C2<20 | |||
Time for the average temperature of other rooms to reach 140℃ C3(s) |
400<C3 | 100≤C3≤400 | C3<100 | |||
Flame spread C4 |
Not spread | Spread to some rooms | Spread to all rooms | |||
Rate of accidents in electrical fire C5(%) |
C5<5 | 5≤C5≤60 | 60<C5 | |||
Flue gas risk B2 |
Peak smoke density C6 (kg/m3) |
C6<1×10-3 | 10-3≤C6≤10-2 | 50×10-3<C6 | ||
Time when visibility is less than 3m C7(s) |
100<C7 | 10≤C7 ≤100 | C7<10 | |||
Total smoke release quality C8(kg) |
C8<0.5 | 0.5≤C8≤5 | 5<C8 | |||
Toxic gas risk B3 |
Time of CO2 reaching dangerous concentration(2000ppm) C9(s) |
100<C9 | 20≤C9≤100 | C9<20 | ||
Time of CO reaching dangerous concentration(800ppm) C10(s) |
100<C10 | 20≤C10≤100 | C10<20 | |||
Peak CO concentration C11(%) |
C11<0.5 | 0.5≤C11≤1 | 1<C11 |