Comprehensive evaluation system and scoring standard of electrical fire risk assessment.

Comprehensive evaluation system of electrical fire risk weight A Criterion layer Index layer 0points 1-9points 10points
Fire combustion risk
B1
Peak heat release rate
C1 (KW)
C1<1500 1500≤C1≤3500 3500<C1
Time for the temperature of the hazard room to reach 200℃
C2(s)
50<C2 20≤C2≤50 C2<20
Time for the average temperature of other rooms to reach 140℃
C3(s)
400<C3 100≤C3≤400 C3<100
Flame spread
C4
Not spread Spread to some rooms Spread to all rooms
Rate of accidents in electrical fire
C5(%)
C5<5 5≤C5≤60 60<C5
Flue gas risk
B2
Peak smoke density
C6 (kg/m3)
C6<1×10-3 10-3≤C6≤10-2 50×10-3<C6
Time when visibility is less than 3m
C7(s)
100<C7 10≤C7 ≤100 C7<10
Total smoke release quality
C8(kg)
C8<0.5 0.5≤C8≤5 5<C8
Toxic gas risk
B3
Time of CO2 reaching dangerous concentration(2000ppm)
C9(s)
100<C9 20≤C9≤100 C9<20
Time of CO reaching dangerous concentration(800ppm)
C10(s)
100<C10 20≤C10≤100 C10<20
Peak CO concentration
C11(%)
C11<0.5 0.5≤C11≤1 1<C11