Setting values and operation time limits of improved ground protection.

Protecting mounting locations Ground protection configuration Protection setting value/A Time limit for action/s
Outlet Circuit Breakers QF1, QF2, QF3 General grounding protection 30 2.6
Highly sensitive grounding protection 3 4.5
Branch Circuit Breakers QF11 General grounding protection 10 2.3
Highly sensitive grounding protection 3 4.2
QF12 General grounding protection 10 2.3
Highly sensitive grounding protection 3 4.2
Boundary circuit breaker QF13 General grounding protection 10 2.0
Highly sensitive grounding protection 3 3.9